Topology: Capacitance Measurement
Models: 101-V; 101-RS ; 101-VRS ; 301-V ; 301-RS ; 301-VRS
	
                    
                 Inputs
                         
                         - Nominal Supply Voltage: 12 or 24 V DC
 
                         - Operating Supply Voltage Range: 10 to 60 V DC
 
                          -  Power Consumption: Max < 1.0 W ( With All Optional Outputs )
 
                           - Reverse Polarity Protection for the Supply Input
 (The Unit will not switch On in this mode): Provided for Infinite Period
 
                        
                         
                          
                         
                        Outputs
                          
                      - Analogue Output: Voltage 0.5 - 4.5 V DC ( as 0 to 100% ) or as required 
 up to 5 V DC
 
 
                      -  Digital Output: RS-485 - Modbus RTU ( Non Isolated ) ( Optional )*
 
                      - Resolution: 0.4 % FSD or 1mm  
 
                      -  Accuracy (Error In Measurement / Non Linearity): +/- 1 % FSD
 
                      -  Repeatability: +/- 0.4 % FSD 
 
                      -  Thermal Accuracy: +/- 1 % max.
 
                      -  Output Short Circuit Protection: Provided. 
 (Short to Supply +Ve and -Ve) **
 
                      -  Indication: Flashing Low and High Level ( For all Models ) 
 ( Used for Calibration Also )
 
                      - Display(Optional*): 3 Digit, 7 Segment Display and Bar graph with 8 Segments 
 
                      - Insulation Resistance (Electrode to Housing): 1 MΩ / 500 VDC. 
 
                      - Operating Mode: Continuous 
 
                    
                      
                     
                        
                        
                        
                          Recommendations and Performance
                         
                        
                        -  Product is to be used only in Liquid Petroleum ( i.e. Diesel ) 
 Products which retain their aggregative state within the operating temperature range 
 
                        
                        -  The use of a poor-quality fuel may result in Measurement Error 
 
                        
                        - The Dielectric Constant of the Medium ( to be Measured ) must be constant. 
 Non-Observance of this requirement will increase the Measurement Error  
 
                         
                         
                         
                         
                          Product Selection Guide
                         
                        
                     -  101-V: Only Analog Output: 0.5 V to 4.5 V DC
 
                     
                     - 101-RS: Only Digital Output: RS-485  
 
                     
                     - 101-VRS: With both Analog and Digital Outputs 
 
                     
                      -  301-V: Display and Analog Output: 0.5 V to 4.5 V DC 
 
                     
                     -  301-RS: Display and Digital Output: RS-485
 
                     
                     -  301-VRS: With Display, Analog and Digital Outputs
 
                         
                         
                        
  Enquire Now