Topology: Capacitance Measurement
Models: 101-V; 101-RS ; 101-VRS ; 301-V ; 301-RS ; 301-VRS
Inputs
- Nominal Supply Voltage: 12 or 24 V DC
- Operating Supply Voltage Range: 10 to 60 V DC
- Power Consumption: Max < 1.0 W ( With All Optional Outputs )
- Reverse Polarity Protection for the Supply Input
(The Unit will not switch On in this mode): Provided for Infinite Period
Outputs
- Analogue Output: Voltage 0.5 - 4.5 V DC ( as 0 to 100% ) or as required
up to 5 V DC
- Digital Output: RS-485 - Modbus RTU ( Non Isolated ) ( Optional )*
- Resolution: 0.4 % FSD or 1mm
- Accuracy (Error In Measurement / Non Linearity): +/- 1 % FSD
- Repeatability: +/- 0.4 % FSD
- Thermal Accuracy: +/- 1 % max.
- Output Short Circuit Protection: Provided.
(Short to Supply +Ve and -Ve) **
- Indication: Flashing Low and High Level ( For all Models )
( Used for Calibration Also )
- Display(Optional*): 3 Digit, 7 Segment Display and Bar graph with 8 Segments
- Insulation Resistance (Electrode to Housing): 1 MΩ / 500 VDC.
- Operating Mode: Continuous
Recommendations and Performance
- Product is to be used only in Liquid Petroleum ( i.e. Diesel )
Products which retain their aggregative state within the operating temperature range
- The use of a poor-quality fuel may result in Measurement Error
- The Dielectric Constant of the Medium ( to be Measured ) must be constant.
Non-Observance of this requirement will increase the Measurement Error
Product Selection Guide
- 101-V: Only Analog Output: 0.5 V to 4.5 V DC
- 101-RS: Only Digital Output: RS-485
- 101-VRS: With both Analog and Digital Outputs
- 301-V: Display and Analog Output: 0.5 V to 4.5 V DC
- 301-RS: Display and Digital Output: RS-485
- 301-VRS: With Display, Analog and Digital Outputs